5.5 : Thermal Distribution Systems
| 5.5.5 |
Typical
Commercial Building Thermal Energy Distribution Design Load Intensities
(Watts per SF) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Distribution
System Fans |
|
|
|
|
|
Other |
|
|
|
|
|
|
|
|
| Central System
Supply Fans |
|
0.3 - 1.0 |
|
Cooling Tower Fan |
|
|
0.1 - 0.3 |
|
| Central System
Return Fans |
|
0.1 - 0.4 |
|
Air-Cooled Chiller Condenser Fan |
|
0.6 |
|
|
| Terminal Box
Fans |
|
|
|
0.5 |
|
|
Exhaust Fans (2) |
|
|
0.05 - 0.3 |
|
| Fan-Coil Unit
Fans (1) |
|
|
0.1 - 0.3 |
|
Condenser Fans |
|
|
|
0.6 |
|
|
| Packaged or
Split System Indoor Blower |
0.6 |
|
|
|
|
|
|
|
|
|
|
|
| Pumps |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Chilled Water
Pump |
|
|
0.1 - 0.3 |
|
|
|
|
|
|
|
|
|
|
| Condenser
Water Pump |
|
0.1 - 0.2 |
|
|
|
|
|
|
|
|
|
|
| Heating Water
Pump |
|
|
0.1 - 0.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|